Specifications Table for ADEQ-A

ADEQ71A7VEB ADEQ100A7VEB ADEQ125A7VEB
Sound pressure level Heating High dBA 37 39 41
    Low dBA 33 34 35
  Cooling Low dBA 33 34 35
    High dBA 37 39 41
Cooling capacity Total capacity Nom. kW 6.8 (1) 9.5 (1) 12.1 (1)
Piping connections Liquid OD mm 9.52 9.52 9.52
  Gas OD mm 15.9 15.9 15.9
  Drain   VP25 (O.D. 32 / I.D. 25) VP25 (O.D. 32 / I.D. 25) VP25 (O.D. 32 / I.D. 25)
Required ceiling void > mm 350 350 350
Power input Cooling Nom. kW 0.350 (1) 0.350 (1) 0.350 (1)
  Heating Nom. kW 0.350 (2) 0.350 (2) 0.350 (2)
Sound power level Cooling dBA 57 62 67
Dimensions Unit Width mm 1,000 1,400 1,400
    Depth mm 700 700 700
    Height mm 300 300 300
Casing Colour   Galvanised steel / Non painted. Galvanised steel / Non painted. Galvanised steel / Non painted.
Weight Unit kg 34 45 45
Drain-up height mm 625 625 625
Heating capacity Total capacity Nom. kW 7.5 (2) 10.8 (2) 13.5 (2)
Notes (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
  (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
  (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
  (4) - The sound pressure values are mentioned for a unit installed with rear suction. (4) - The sound pressure values are mentioned for a unit installed with rear suction. (4) - The sound pressure values are mentioned for a unit installed with rear suction.
  (5) - PED unit category: Art3§3: excluded from scope of PED due to article 1, item 3.6 of 97/23/EC (5) - PED unit category: Art3§3: excluded from scope of PED due to article 1, item 3.6 of 97/23/EC (5) - PED unit category: Art3§3: excluded from scope of PED due to article 1, item 3.6 of 97/23/EC