ADEQ71A7VEB |
ADEQ100A7VEB |
ADEQ125A7VEB |
Sound pressure level
|
Heating
|
High
|
dBA
|
37
|
39
|
41
|
|
|
Low
|
dBA
|
33
|
34
|
35
|
|
Cooling
|
Low
|
dBA
|
33
|
34
|
35
|
|
|
High
|
dBA
|
37
|
39
|
41
|
Cooling capacity
|
Total capacity
|
Nom.
|
kW
|
6.8 (1)
|
9.5 (1)
|
12.1 (1)
|
Piping connections
|
Liquid
|
OD
|
mm
|
9.52
|
9.52
|
9.52
|
|
Gas
|
OD
|
mm
|
15.9
|
15.9
|
15.9
|
|
Drain
|
|
VP25 (O.D. 32 / I.D. 25)
|
VP25 (O.D. 32 / I.D. 25)
|
VP25 (O.D. 32 / I.D. 25)
|
Required ceiling void >
|
mm
|
350
|
350
|
350
|
Power input
|
Cooling
|
Nom.
|
kW
|
0.350 (1)
|
0.350 (1)
|
0.350 (1)
|
|
Heating
|
Nom.
|
kW
|
0.350 (2)
|
0.350 (2)
|
0.350 (2)
|
Sound power level
|
Cooling
|
dBA
|
57
|
62
|
67
|
Dimensions
|
Unit
|
Width
|
mm
|
1,000
|
1,400
|
1,400
|
|
|
Depth
|
mm
|
700
|
700
|
700
|
|
|
Height
|
mm
|
300
|
300
|
300
|
Casing
|
Colour
|
|
Galvanised steel / Non painted.
|
Galvanised steel / Non painted.
|
Galvanised steel / Non painted.
|
Weight
|
Unit
|
kg
|
34
|
45
|
45
|
Drain-up height
|
mm
|
625
|
625
|
625
|
Heating capacity
|
Total capacity
|
Nom.
|
kW
|
7.5 (2)
|
10.8 (2)
|
13.5 (2)
|
Notes
|
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
|
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
|
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
|
|
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
|
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
|
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
|
|
(3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
|
(3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
|
(3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
|
|
(4) - The sound pressure values are mentioned for a unit installed with rear suction.
|
(4) - The sound pressure values are mentioned for a unit installed with rear suction.
|
(4) - The sound pressure values are mentioned for a unit installed with rear suction.
|
|
(5) - PED unit category: Art3§3: excluded from scope of PED due to article 1, item 3.6 of 97/23/EC
|
(5) - PED unit category: Art3§3: excluded from scope of PED due to article 1, item 3.6 of 97/23/EC
|