| EHSXB16P50AA / ERLQ011CAW1 | EHSXB16P50AA / ERLQ014CAW1 | EHSXB16P50AA / ERLQ016CAW1 | ||||
|---|---|---|---|---|---|---|
| Domestic hot water heating | General | Declared load profile | XL | XL | XL | |
| Average climate | Water heating energy efficiency class | A | A | A | ||
| COP | 4.38 (1), 3.32 (2), 2.45 (3), 3.29 (4) | 4.27 (1), 3.34 (2), 2.58 (3), 3.22 (4) | 4.10 (1), 3.22 (2), 2.44 (3), 3.15 (4) | |||
| Indoor unit | EHSXB16P50AA | EHSXB16P50AA | EHSXB16P50AA | |||
| Cooling capacity | Nom. | kW | 15.1 (1), 11.7 (2) | 16.1 (1), 12.6 (2) | 16.8 (1), 13.1 (2) | |
| Min. | kW | 2.5 (1), 2.6 (2) | 2.5 (1), 2.6 (2) | |||
| Max. | kW | 15.1 (1), 11.7 (2) | 16.1 (1), 12.6 (2) | 16.8 (1), 13.1 (2) | ||
| EER | 3.32 (1), 2.72 (2) | 2.96 (1), 2.47 (2) | 2.72 (1), 2.29 (2) | |||
| Heating capacity | Nom. | kW | 11.80 (1), 10.40 (2), 5.95 (3), 7.74 (4) | 14.81 (1), 13.73 (2), 8.28 (3), 9.57 (4) | 15.34 (1), 14.86 (2), 8.04 (3), 10.05 (4) | |
| Max. | kW | 11.38 (1), 11.00 (2) | 14.55 (1), 13.59 (2) | 16.10 (1), 15.22 (2) | ||
| Power input | Heating | Max. | kW | 2.64 (1), 3.25 (2) | 3.43 (1), 4.22 (2) | 3.83 (1), 4.71 (2) |
| Nom. | kW | 2.57 (1), 3.13 (2), 2.43 (3), 2.35 (4) | 3.42 (1), 4.07 (2), 3.17 (3), 2.93 (4) | 3.42 (1), 4.07 (2), 3.17 (3), 2.93 (4) | ||
| Cooling | Nom. | kW | 4.55 (1), 4.30 (2) | 5.44 (1), 5.10 (2) | 6.18 (1), 5.72 (2) | |
| Max. | kW | 4.53 (1), 4.31 (2) | 5.42 (1), 5.09 (2) | 6.15 (1), 5.74 (2) | ||
| Notes | (1) - Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) | (1) - Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) | (1) - Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) | |||
| (2) - Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C ) | (2) - Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C ) | (2) - Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C ) | ||||
| (3) - EW 30°C; LW 35°C; ambient conditions: -7°CDB/-8°CWB | (3) - EW 30°C; LW 35°C; ambient conditions: -7°CDB/-8°CWB | (3) - EW 30°C; LW 35°C; ambient conditions: -7°CDB/-8°CWB | ||||
| (4) - EW 30°C; LW 35°C; ambient conditions: 2°CDB/1°CWB | (4) - EW 30°C; LW 35°C; ambient conditions: 2°CDB/1°CWB | (4) - EW 30°C; LW 35°C; ambient conditions: 2°CDB/1°CWB | ||||
| (5) - Tamb 35°C - LWE 18°C (DT=5°C) | (5) - Tamb 35°C - LWE 18°C (DT=5°C) | (5) - Tamb 35°C - LWE 18°C (DT=5°C) | ||||
| (6) - Tamb 35°C - LWE 7°C (DT=5°C) | (6) - Tamb 35°C - LWE 7°C (DT=5°C) | (6) - Tamb 35°C - LWE 7°C (DT=5°C) | ||||
| (7) - DB/WB 7°C/6°C - LWC 35°C (DT=5°C) | (7) - DB/WB 7°C/6°C - LWC 35°C (DT=5°C) | (7) - DB/WB 7°C/6°C - LWC 35°C (DT=5°C) | ||||
| (8) - DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) | (8) - DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) | (8) - DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) | ||||