Specifications Table for EHVZ-CB3V / ERLQ-CV3

EHVZ08S18CB3V / ERLQ008CAV3
Domestic hot water heating General Declared load profile   L
  Average climate Water heating energy efficiency class   A
COP 4.45 (1), 3.42 (2)
Heating capacity Nom. kW 7.40 (1), 6.89 (2)
  Min. kW 1.80 (1)
  Max. kW 10.0 (1), 9.53 (2)
Power input Heating Nom. kW 1.66 (1), 2.01 (2)
Notes (1) - Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
  (2) - Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C )
  (3) - Condition 3: heating Ta DB -7°C (RH85%) - LWC 35°C
  (4) - Condition 4: heating Ta DB -7°C (RH85%) - LWC 45°C
  (5) - Capacity must be split up over the additional and main zone. Refer to ESP-data for more details on available head (kPa).
  (6) - DB/WB 7°C/6°C - LWC 35°C (DT=5°C)
  (7) - DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
  (8) - 15°C-25°C: BUH only, no heat pump operation = during commissioning