EKHVH008BB6V3 |
EKHVH008BB6WN |
EKHVH008BB9WN |
EKHVH016BB6V3 |
EKHVH016BB6WN |
EKHVH016BB9WN |
Sound pressure level
|
Medium speed
|
0 ESP
|
dBA
|
28 (9)
|
28 (9)
|
28 (9)
|
28 (15)
|
28 (15)
|
28 (15)
|
Sound power level
|
Medium speed
|
0 ESP
|
dBA
|
42
|
42
|
42
|
46
|
46
|
46
|
Dimensions
|
Unit
|
Width
|
mm
|
600
|
600
|
600
|
600
|
600
|
600
|
|
|
Depth
|
mm
|
695
|
695
|
695
|
695
|
695
|
695
|
|
|
Height
|
mm
|
705
|
705
|
705
|
705
|
705
|
705
|
Casing
|
Material
|
|
Precoated sheet metal
|
Precoated sheet metal
|
Precoated sheet metal
|
Precoated sheet metal
|
Precoated sheet metal
|
Precoated sheet metal
|
|
Colour
|
|
Metallic grey
|
Metallic grey
|
Metallic grey
|
Metallic grey
|
Metallic grey
|
Metallic grey
|
Weight
|
Unit
|
kg
|
65
|
65
|
65
|
67
|
67
|
67
|
Wiring connections
|
For connection with user interface
|
Remark
|
|
Cable section minimum 0.75mm², maximum length 500m
|
Cable section minimum 0.75mm², maximum length 500m
|
Cable section minimum 0.75mm², maximum length 500m
|
Cable section minimum 0.75mm², maximum length 500m
|
Cable section minimum 0.75mm², maximum length 500m
|
Cable section minimum 0.75mm², maximum length 500m
|
|
|
Quantity
|
|
2
|
2
|
2
|
2
|
2
|
2
|
Electric heater
|
Current back-up heater
|
Running current
|
A
|
26 (18)
|
8.7 (19)
|
13 (20)
|
26 (24)
|
8.7 (25)
|
13 (26)
|
|
Power supply
|
Frequency
|
Hz
|
50
|
50
|
50
|
|
|
Voltage
|
V
|
230
|
400
|
400
|
230
|
400
|
400
|
|
|
Phase
|
|
1~
|
3~
|
3~
|
1~
|
3~
|
3~
|
Notes
|
(1) - In combination with ERHQ006BAV3
|
(1) - In combination with ERHQ006BAV3
|
(1) - In combination with ERHQ006BAV3
|
(1) - In combination with ERHQ011BAV3
|
(1) - In combination with ERHQ011BAV3
|
(1) - In combination with ERHQ011BAV3
|
|
(2) - In combination with ERLQ006BAV3
|
(2) - In combination with ERLQ006BAV3
|
(2) - In combination with ERLQ006BAV3
|
(2) - In combination with ERLQ011BAV3
|
(2) - In combination with ERLQ011BAV3
|
(2) - In combination with ERLQ011BAV3
|
|
(3) - In combination with ERHQ007BAV3
|
(3) - In combination with ERHQ007BAV3
|
(3) - In combination with ERHQ007BAV3
|
(3) - In combination with ERHQ011BAW1
|
(3) - In combination with ERHQ011BAW1
|
(3) - In combination with ERHQ011BAW1
|
|
(4) - In combination with ERLQ007BAV3
|
(4) - In combination with ERLQ007BAV3
|
(4) - In combination with ERLQ007BAV3
|
(4) - In combination with ERLQ011BAW1
|
(4) - In combination with ERLQ011BAW1
|
(4) - In combination with ERLQ011BAW1
|
|
(5) - In combination with ERHQ008BAV3
|
(5) - In combination with ERHQ008BAV3
|
(5) - In combination with ERHQ008BAV3
|
(5) - In combination with ERHQ014BAV3
|
(5) - In combination with ERHQ014BAV3
|
(5) - In combination with ERHQ014BAV3
|
|
(6) - In combination with ERLQ008BAV3
|
(6) - In combination with ERLQ008BAV3
|
(6) - In combination with ERLQ008BAV3
|
(6) - In combination with ERLQ014BAV3
|
(6) - In combination with ERLQ014BAV3
|
(6) - In combination with ERLQ014BAV3
|
|
(7) - Tamb 35°C - LWE 7°C (Dt=5°C) at high speed
|
(7) - Tamb 35°C - LWE 7°C (Dt=5°C) at high speed
|
(7) - Tamb 35°C - LWE 7°C (Dt=5°C) at high speed
|
(7) - In combination with ERHQ014BAW1
|
(7) - In combination with ERHQ014BAW1
|
(7) - In combination with ERHQ014BAW1
|
|
(8) - DB/WB 7°C/6°C - LWC 35°C (Dt=5°C) at high speed
|
(8) - DB/WB 7°C/6°C - LWC 35°C (Dt=5°C) at high speed
|
(8) - DB/WB 7°C/6°C - LWC 35°C (Dt=5°C) at high speed
|
(8) - In combination with ERLQ014BAW1
|
(8) - In combination with ERLQ014BAW1
|
(8) - In combination with ERLQ014BAW1
|
|
(9) - The sound pressure level is measured via a microphone at a 1m distance from the unit. It is a relative value, depending on the distance and acoustic environment.
|
(9) - The sound pressure level is measured via a microphone at a 1m distance from the unit. It is a relative value, depending on the distance and acoustic environment.
|
(9) - The sound pressure level is measured via a microphone at a 1m distance from the unit. It is a relative value, depending on the distance and acoustic environment.
|
(9) - In combination with ERHQ016BAV3
|
(9) - In combination with ERHQ016BAV3
|
(9) - In combination with ERHQ016BAV3
|
|
(10) - The sound pressure level mentioned is valid for pump medium speed - 0 ESP / medium speed - nominal flow / high speed - nominal flow
|
(10) - The sound pressure level mentioned is valid for pump medium speed - 0 ESP / medium speed - nominal flow / high speed - nominal flow
|
(10) - The sound pressure level mentioned is valid for pump medium speed - 0 ESP / medium speed - nominal flow / high speed - nominal flow
|
(10) - In combination with ERLQ016BAV3
|
(10) - In combination with ERLQ016BAV3
|
(10) - In combination with ERLQ016BAV3
|
|
(11) - 15°C-25°C: BUH only, no heat pump operation = during commissioning
|
(11) - 15°C-25°C: BUH only, no heat pump operation = during commissioning
|
(11) - 15°C-25°C: BUH only, no heat pump operation = during commissioning
|
(11) - In combination with ERHQ016BAW1
|
(11) - In combination with ERHQ016BAW1
|
(11) - In combination with ERHQ016BAW1
|
|
(12) - Including piping + PHE + back-up heater; excluding expansion vessel
|
(12) - Including piping + PHE + back-up heater; excluding expansion vessel
|
(12) - Including piping + PHE + back-up heater; excluding expansion vessel
|
(12) - In combination with ERLQ016BAW1
|
(12) - In combination with ERLQ016BAW1
|
(12) - In combination with ERLQ016BAW1
|
|
(13) - See separate drawing for operation range
|
(13) - See separate drawing for operation range
|
(13) - See separate drawing for operation range
|
(13) - Tamb 35°C - LWE 7°C (Dt=5°C) at high speed
|
(13) - Tamb 35°C - LWE 7°C (Dt=5°C) at high speed
|
(13) - Tamb 35°C - LWE 7°C (Dt=5°C) at high speed
|
|
(14) - Operation range: only with optional *KHTS* tank. Water temperatures higher than 50°C are with BUH only. More details, see operation range drawnig
|
(14) - Operation range: only with optional *KHTS* tank. Water temperatures higher than 50°C are with BUH only. More details, see operation range drawnig
|
(14) - Operation range: only with optional *KHTS* tank. Water temperatures higher than 50°C are with BUH only. More details, see operation range drawnig
|
(14) - DB/WB 7°C/6°C - LWC 35°C (Dt=5°C) at high speed
|
(14) - DB/WB 7°C/6°C - LWC 35°C (Dt=5°C) at high speed
|
(14) - DB/WB 7°C/6°C - LWC 35°C (Dt=5°C) at high speed
|
|
(15) - Above mentioned power supply of the hydrobox is for the backup heater only. The switch box and the pump of the hydrobox are supplied via the outdoor unit.
|
(15) - Above mentioned power supply of the hydrobox is for the backup heater only. The switch box and the pump of the hydrobox are supplied via the outdoor unit.
|
(15) - Above mentioned power supply of the hydrobox is for the backup heater only. The switch box and the pump of the hydrobox are supplied via the outdoor unit.
|
(15) - The sound pressure level is measured via a microphone at a 1m distance from the unit. It is a relative value, depending on the distance and acoustic environment.
|
(15) - The sound pressure level is measured via a microphone at a 1m distance from the unit. It is a relative value, depending on the distance and acoustic environment.
|
(15) - The sound pressure level is measured via a microphone at a 1m distance from the unit. It is a relative value, depending on the distance and acoustic environment.
|
|
(16) - Electric heater has 2 capacity steps
|
(16) - Electric heater has 2 capacity steps
|
(16) - Electric heater has 2 capacity steps
|
(16) - The sound pressure level mentioned is valid for pump medium speed - 0 ESP / medium speed - nominal flow / high speed - nominal flow
|
(16) - The sound pressure level mentioned is valid for pump medium speed - 0 ESP / medium speed - nominal flow / high speed - nominal flow
|
(16) - The sound pressure level mentioned is valid for pump medium speed - 0 ESP / medium speed - nominal flow / high speed - nominal flow
|
|
(17) - In accordance with EN/IEC 61000-3-11, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys (system impedance) ≤ Zmax
|
(17) - In accordance with EN/IEC 61000-3-11, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys (system impedance) ≤ Zmax
|
(17) - In accordance with EN/IEC 61000-3-11, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys (system impedance) ≤ Zmax
|
(17) - 15°C-25°C: BUH only, no heat pump operation = during commissioning
|
(17) - 15°C-25°C: BUH only, no heat pump operation = during commissioning
|
(17) - 15°C-25°C: BUH only, no heat pump operation = during commissioning
|
|
(18) - The installer can reduce the capacity of the heater from 6 to 3kW. The current is then reduced from 26 to 13A. Please refer to the installation manual for instructions.
|
(18) - The installer can reduce the capacity of the heater from 6 to 3kW. The current is then reduced from 26 to 13A. Please refer to the installation manual for instructions.
|
(18) - The installer can reduce the capacity of the heater from 6 to 3kW. The current is then reduced from 26 to 13A. Please refer to the installation manual for instructions.
|
(18) - Including piping + PHE + back-up heater; excluding expansion vessel
|
(18) - Including piping + PHE + back-up heater; excluding expansion vessel
|
(18) - Including piping + PHE + back-up heater; excluding expansion vessel
|
|
(19) - The installer can reduce the capacity of the heater from 6 to 2kW. The current is then reduced from 8.7 to 5A. Please refer to the installation manual for instructions.
|
(19) - The installer can reduce the capacity of the heater from 6 to 2kW. The current is then reduced from 8.7 to 5A. Please refer to the installation manual for instructions.
|
(19) - The installer can reduce the capacity of the heater from 6 to 2kW. The current is then reduced from 8.7 to 5A. Please refer to the installation manual for instructions.
|
(19) - See operation range drawing for difference between single & three phase units
|
(19) - See operation range drawing for difference between single & three phase units
|
(19) - See operation range drawing for difference between single & three phase units
|
|
(20) - The installer can reduce the capacity of the heater from 9 to 3kW. The current is then reduced from 13 to 7.5A. Please refer to the installation manual for instructions.
|
(20) - The installer can reduce the capacity of the heater from 9 to 3kW. The current is then reduced from 13 to 7.5A. Please refer to the installation manual for instructions.
|
(20) - The installer can reduce the capacity of the heater from 9 to 3kW. The current is then reduced from 13 to 7.5A. Please refer to the installation manual for instructions.
|
(20) - Operation range: only with optional *KHTS* tank. Water temperatures higher than 55°C are with BUH only. More details, see operation range drawnig
|
(20) - Operation range: only with optional *KHTS* tank. Water temperatures higher than 55°C are with BUH only. More details, see operation range drawnig
|
(20) - Operation range: only with optional *KHTS* tank. Water temperatures higher than 55°C are with BUH only. More details, see operation range drawnig
|
|
(21) - EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A
|
(21) - EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A
|
(21) - EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A
|
(21) - Above mentioned power supply of the hydrobox is for the backup heater only. The switch box and the pump of the hydrobox are supplied via the outdoor unit.
|
(21) - Above mentioned power supply of the hydrobox is for the backup heater only. The switch box and the pump of the hydrobox are supplied via the outdoor unit.
|
(21) - Above mentioned power supply of the hydrobox is for the backup heater only. The switch box and the pump of the hydrobox are supplied via the outdoor unit.
|
|
(22) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase
|
(22) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase
|
(22) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase
|
(22) - Optional electric heater has 2 capacity steps except for the 3V3 model which has only 1 capacity step.
|
(22) - Optional electric heater has 2 capacity steps except for the 3V3 model which has only 1 capacity step.
|
(22) - Optional electric heater has 2 capacity steps except for the 3V3 model which has only 1 capacity step.
|
|
|
|
|
(23) - In accordance with EN/IEC 61000-3-11, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys (system impedance) ≤ Zmax
|
(23) - In accordance with EN/IEC 61000-3-11, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys (system impedance) ≤ Zmax
|
(23) - In accordance with EN/IEC 61000-3-11, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys (system impedance) ≤ Zmax
|
|
|
|
|
(24) - The installer can reduce the capacity of the heater from 6 to 3kW. The current is then reduced from 26 to 13A. Please refer to the installation manual for instructions.
|
(24) - The installer can reduce the capacity of the heater from 6 to 3kW. The current is then reduced from 26 to 13A. Please refer to the installation manual for instructions.
|
(24) - The installer can reduce the capacity of the heater from 6 to 3kW. The current is then reduced from 26 to 13A. Please refer to the installation manual for instructions.
|
|
|
|
|
(25) - The installer can reduce the capacity of the heater from 6 to 2kW. The current is then reduced from 8.7 to 5A. Please refer to the installation manual for instructions.
|
(25) - The installer can reduce the capacity of the heater from 6 to 2kW. The current is then reduced from 8.7 to 5A. Please refer to the installation manual for instructions.
|
(25) - The installer can reduce the capacity of the heater from 6 to 2kW. The current is then reduced from 8.7 to 5A. Please refer to the installation manual for instructions.
|
|
|
|
|
(26) - The installer can reduce the capacity of the heater from 6 to 3kW. The current is then reduced from 13 to 7.5A. Please refer to the installation manual for instructions.
|
(26) - The installer can reduce the capacity of the heater from 6 to 3kW. The current is then reduced from 13 to 7.5A. Please refer to the installation manual for instructions.
|
(26) - The installer can reduce the capacity of the heater from 6 to 3kW. The current is then reduced from 13 to 7.5A. Please refer to the installation manual for instructions.
|
|
|
|
|
(27) - EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A
|
(27) - EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A
|
(27) - EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A
|
|
|
|
|
(28) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase
|
(28) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase
|
(28) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase
|