| FFQ25B9V1B | FFQ35B9V1B | FFQ50B9V1B | FFQ60B9V1B | ||||
|---|---|---|---|---|---|---|---|
| Sound pressure level | Cooling | Low | dBA | 24.5 | 25 | 27 | 32 |
| High | dBA | 29.5 | 32 | 36 | 41 | ||
| Standard Accessories | Operation manual | Operation manual | Operation manual | Operation manual | Operation manual | ||
| Installation manual | Installation manual | Installation manual | Installation manual | Installation manual | |||
| Paper pattern for installation | Paper pattern for installation | Paper pattern for installation | Paper pattern for installation | Paper pattern for installation | |||
| Drain hose | Drain hose | Drain hose | Drain hose | Drain hose | |||
| Clamp metal | Clamp metal | Clamp metal | Clamp metal | Clamp metal | |||
| Washer fixing plate | Washer fixing plate | Washer fixing plate | Washer fixing plate | Washer fixing plate | |||
| Sealing pads | Sealing pads | Sealing pads | Sealing pads | Sealing pads | |||
| Clamps | Clamps | Clamps | Clamps | Clamps | |||
| Screws | Screws | Screws | Screws | Screws | |||
| Washer for hanger bracket | Washer for hanger bracket | Washer for hanger bracket | Washer for hanger bracket | Washer for hanger bracket | |||
| Insulation for fitting | Insulation for fitting | Insulation for fitting | Insulation for fitting | Insulation for fitting | |||
| Cooling capacity | Total capacity | Nom. | kW | 2.5 (1) | 3.4 (1) | 4.7 (1) | 5.8 (1) |
| Piping connections | Liquid | OD | mm | 6.35 | 6.35 | 6.35 | 6.35 |
| Gas | OD | mm | 9.52 | 9.52 | 12.7 | 12.7 | |
| Drain | VP20 (I.D. 20/O.D. 26) | VP20 (I.D. 20/O.D. 26) | VP20 (I.D. 20/O.D. 26) | VP20 (I.D. 20/O.D. 26) | |||
| Sound power level | Cooling | dBA | 46.5 | 49 | 53 | 58 | |
| Dimensions | Unit | Width | mm | 575 | 575 | 575 | 575 |
| Depth | mm | 575 | 575 | 575 | 575 | ||
| Height | mm | 286 | 286 | 286 | 286 | ||
| Casing | Material | Galvanised steel | Galvanised steel | Galvanised steel | Galvanised steel | ||
| Colour | Unpainted | Unpainted | Unpainted | Unpainted | |||
| Weight | Unit | kg | 17.5 | 17.5 | 17.5 | 17.5 | |
| Decoration panel | Weight | kg | 2.7 | 2.7 | 2.7 | 2.7 | |
| Model | BYFQ60BW1 | BYFQ60BW1 | BYFQ60BW1 | BYFQ60BW1 | |||
| Dimensions | Height | mm | 55 | 55 | 55 | 55 | |
| Depth | mm | 700 | 700 | 700 | 700 | ||
| Width | mm | 700 | 700 | 700 | 700 | ||
| Colour | Pure White (RAL 9010) | Pure White (RAL 9010) | Pure White (RAL 9010) | Pure White (RAL 9010) | |||
| Heating capacity | Total capacity | Nom. | kW | 3.2 (2) | 4.5 (2) | 5.5 (2) | 7.0 (2) |
| Power supply | Phase | 1~ | 1~ | 1~ | 1~ | ||
| Name | V1 | V1 | V1 | V1 | |||
| Frequency | Hz | 50 | 50 | 50 | 50 | ||
| Voltage | V | 220-240 | 220-240 | 220-240 | 220-240 | ||
| Notes | (1) - Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0m | |||
| (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m | ||||
| (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. | (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. | (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. | (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. | ||||
| (4) - Nominal cooling and heating capactity is depending on the outdoor unit type | (4) - Nominal cooling and heating capactity is depending on the outdoor unit type | (4) - Nominal cooling and heating capactity is depending on the outdoor unit type | (4) - Nominal cooling and heating capactity is depending on the outdoor unit type | ||||
| (5) - PED unit category: Art3§3: excluded from scope of PED due to article 1, item 3.6 of 97/23/EC | (5) - PED unit category: Art3§3: excluded from scope of PED due to article 1, item 3.6 of 97/23/EC | (5) - PED unit category: Art3§3: excluded from scope of PED due to article 1, item 3.6 of 97/23/EC | (5) - PED unit category: Art3§3: excluded from scope of PED due to article 1, item 3.6 of 97/23/EC | ||||