FFQ25B8V1B |
FFQ35B8V1B |
FFQ50B8V1B |
FFQ60B8V1B |
Dimensions
|
Unit
|
Height
|
mm
|
286
|
286
|
286
|
286
|
|
|
Width
|
mm
|
575
|
575
|
575
|
575
|
|
|
Depth
|
mm
|
575
|
575
|
575
|
575
|
Weight
|
Unit
|
kg
|
17.5
|
17.5
|
17.5
|
17.5
|
Fan
|
Air flow rate
|
Cooling
|
High
|
m³/min
|
9.0
|
10.0
|
12.0
|
15.0
|
|
|
|
Low
|
m³/min
|
6.5
|
6.5
|
8.0
|
10.0
|
|
|
Heating
|
High
|
m³/min
|
9.0
|
10.0
|
12.0
|
15.0
|
|
|
|
Low
|
m³/min
|
6.5
|
6.5
|
8.0
|
10.0
|
Sound power level
|
Cooling
|
dBA
|
46.5
|
49.0
|
53.0
|
58.0
|
Sound pressure level
|
Cooling
|
High
|
dBA
|
29.5
|
32.0
|
36.0
|
41.0
|
|
|
Low
|
dBA
|
24.5
|
25.0
|
27.0
|
32.0
|
|
Heating
|
High
|
dBA
|
29.5
|
32.0
|
36.0
|
41.0
|
|
|
Low
|
dBA
|
24.5
|
25.0
|
27.0
|
32.0
|
Piping connections
|
Liquid
|
OD
|
mm
|
6.35
|
6.35
|
6.35
|
6.35
|
|
Gas
|
OD
|
mm
|
9.52
|
9.52
|
12.7
|
12.7
|
|
Drain
|
|
26
|
26
|
26
|
26
|
Decoration panel
|
Model
|
|
BYFQ60BAW1
|
BYFQ60BAW1
|
BYFQ60BAW1
|
BYFQ60BAW1
|
|
Colour
|
|
Pure White (RAL 9010)
|
Pure White (RAL 9010)
|
Pure White (RAL 9010)
|
Pure White (RAL 9010)
|
|
Dimensions
|
Height
|
mm
|
55
|
55
|
55
|
55
|
|
|
Width
|
mm
|
700
|
700
|
700
|
700
|
|
|
Depth
|
mm
|
700
|
700
|
700
|
700
|
|
Weight
|
kg
|
2.7
|
2.7
|
2.7
|
2.7
|
Standard Accessories
|
Installation and operation manual
|
1
|
1
|
1
|
1
|
|
Drain hose
|
1
|
1
|
1
|
1
|
|
Clamp for drain hose
|
1
|
1
|
1
|
1
|
|
Washer for hanger bracket
|
8
|
8
|
8
|
8
|
|
Big clamp
|
6
|
6
|
6
|
6
|
|
Small clamp
|
1
|
1
|
1
|
1
|
|
Paper pattern for installation
|
1
|
1
|
1
|
1
|
|
Screws
|
4
|
4
|
4
|
4
|
|
Washer fixing plate
|
4
|
4
|
4
|
4
|
|
Insulation for fitting for gas pipe
|
1
|
1
|
1
|
1
|
|
Insulation for fitting for liquid pipe
|
1
|
1
|
1
|
1
|
|
Sealing pad (large)
|
1
|
1
|
1
|
1
|
|
Sealing pad (small)
|
1
|
1
|
1
|
1
|
|
Sealing material
|
2
|
2
|
2
|
2
|
Power supply
|
Name
|
|
V1
|
V1
|
V1
|
V1
|
|
Phase
|
|
1~
|
1~
|
1~
|
1~
|
|
Frequency
|
Hz
|
50
|
50
|
50
|
50
|
|
Voltage
|
V
|
230
|
230
|
230
|
230
|
Notes
|
(1) - Sound values are measured in an anechoic room.
|
(1) - Sound values are measured in an anechoic room.
|
(1) - Sound values are measured in an anechoic room.
|
(1) - Sound values are measured in an anechoic room.
|
|
(2) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
|
(2) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
|
(2) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
|
(2) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
|
|
(3) - The sound power level is an absolute value indicating the power which a sound source generates.
|
(3) - The sound power level is an absolute value indicating the power which a sound source generates.
|
(3) - The sound power level is an absolute value indicating the power which a sound source generates.
|
(3) - The sound power level is an absolute value indicating the power which a sound source generates.
|