Specifications Table for FVA-A / RZAG-MV1

FVA100AMVEB / RZAG71M7V1B FVA71AMVEB / RZAG71M7V1B FVA100AMVEB / RZAG100M7V1B FVA140AMVEB / RZAG100M7V1B FVA125AMVEB / RZAG125M7V1B FVA140AMVEB / RZAG140M7V1B
Cooling capacity Nom. kW   6.80 (1) 9.50 (1) 9.50 (1) 12.1 (1) 13.4 (1)
Space cooling Annual energy consumption kWh/a   374 554 517 1,133 1,314
  Capacity Pdesign kW   6.80 9.50 9.50 12.1 13.4
Space heating (Average climate) Capacity Pdesign kW   4.70 7.80 7.80 9.52 9.52
  Annual energy consumption kWh/a   1,625 2,600 2,697 3,209 3,383
Heating capacity Nom. kW   7.50 (2) 10.8 (2) 10.8 (2) 13.5 (2) 15.5 (2)
Energy Efficiency Range A+++ ~ D
Space cooling SEER     6.37 6.00 6.43 6.41 6.12
  Energy efficiency class     A++ A+ A++
Space heating (Average climate) SCOP/A     4.05 4.20 4.05 4.15 3.94
  Energy efficiency class     A+ A+ A+
Notes   (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Cooling: T2: indoor temp. 26,6°CDB, 19,4°CWB, outdoor temp. 48°CDB [Btu/hr/W] (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m.
    (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.
    (3) - See separate drawing for operation range (3) - See separate drawing for operation range   (3) - See separate drawing for operation range (3) - See separate drawing for operation range