Specifications Table for RR-BV3

RR71B8V3B RR71B2V3B RR100B8V3B
Sound pressure level Cooling Nom. dBA 50.0 50.0 53.0
Standard Accessories Declaration of conformity 1 1 1
  Installation manual 1 1 1
Refrigerant Charge kg 2.70 2.70 3.70
  Type   R-410A R-410A R-410A
Operation range Cooling Ambient Max. °CDB 46.0 46.0 46.0
      Min. °CDB -15.0 -15.0 -15.0
Piping connections Piping length OU - IU Max. m 70 70 70
    System Chargeless m 30 30 30
      Equivalent m 90 90 90
  Level difference IU - IU Max. m 0.5 0.5 0.5
    IU - OU Max. m 30.0 30.0 30.0
Sound power level Cooling dBA 63.0 63.0 66.0
Dimensions Unit Width mm 900 900 900
    Depth mm 320 320 320
    Height mm 770 770 1,170
Compressor Type   Hermetically sealed scroll compressor Hermetically sealed scroll compressor Hermetically sealed scroll compressor
Weight Unit kg 83 83 102
Power supply Phase   1~ 1~ 1~
  Frequency Hz 50 50 50
  Voltage V 230 230 230
Notes (1) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (1) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (1) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
  (2) - The sound power level is an absolute value indicating the power which a sound source generates. (2) - The sound power level is an absolute value indicating the power which a sound source generates. (2) - The sound power level is an absolute value indicating the power which a sound source generates.
  (3) - Sound values are measured in a semi-anechoic room. (3) - Sound values are measured in a semi-anechoic room. (3) - Sound values are measured in a semi-anechoic room.
  (4) - Heating capacity is only applicable for combination with heat pump outdoor unit (4) - Heating capacity is only applicable for combination with heat pump outdoor unit (4) - Heating capacity is only applicable for combination with heat pump outdoor unit
  (5) - In case of drain piping for the outdoor unit, a drain piping kit (option) is needed. (5) - In case of drain piping for the outdoor unit, a drain piping kit (option) is needed. (5) - In case of drain piping for the outdoor unit, a drain piping kit (option) is needed.
  (6) - Minimum Ssc value: Equipment complying with EN/IEC 61000-3-12: European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and ≤ 75A per phase (6) - Minimum Ssc value: Equipment complying with EN/IEC 61000-3-12: European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and ≤ 75A per phase (6) - Minimum Ssc value: Equipment complying with EN/IEC 61000-3-12: European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and ≤ 75A per phase