| RZQS71D7V1B | RZQS100D7V1B | RZQS125D7V1B | RZQS140D7V1B | |||||
|---|---|---|---|---|---|---|---|---|
| Sound pressure level | Heating | Nom. | dBA | 51 | 55 | 53 | 54 | |
| Cooling | Nom. | dBA | 49 | 51 | 51 | 52 | ||
| Night quiet mode | Level 1 | dBA | 47 | 49 | 49 | 50 | ||
| Standard Accessories | Tie-wraps | 2 | 2 | 2 | 2 | |||
| Installation manual | 1 | 1 | 1 | 1 | ||||
| Refrigerant | Charge | TCO2Eq | 5.7 | 7.7 | 7.7 | 7.7 | ||
| GWP | 2,087.5 | 2,087.5 | 2,087.5 | 2,087.5 | ||||
| Charge | kg | 2.75 | 3.7 | 3.7 | 3.7 | |||
| Type | R-410A | R-410A | R-410A | R-410A | ||||
| Piping connections | Liquid | OD | mm | 9.52 | 9.52 | 9.52 | 9.52 | |
| Piping length | OU - IU | Max. | m | 30 | 50 | 50 | 50 | |
| System | Chargeless | m | 30 | 30 | 30 | 30 | ||
| Equivalent | m | 40 | 70 | 70 | 70 | |||
| Gas | OD | mm | 15.9 | 15.9 | 15.9 | 15.9 | ||
| Level difference | IU - IU | Max. | m | 0.5 | 0.5 | 0.5 | 0.5 | |
| IU - OU | Max. | m | 15 | 30 | 30 | 30 | ||
| Additional refrigerant charge | kg/m | See installation manual 4PW49302-1 | See installation manual 4PW49302-1 | See installation manual 4PW49302-1 | See installation manual 4PW49302-1 | |||
| Sound power level | Cooling | dBA | 65 | 67 | 67 | 68 | ||
| Dimensions | Unit | Width | mm | 900 | 900 | 900 | 900 | |
| Depth | mm | 320 | 320 | 320 | 320 | |||
| Height | mm | 770 | 1,170 | 1,170 | 1,170 | |||
| Compressor | Type | Hermetically sealed swing compressor | Hermetically sealed scroll compressor | Hermetically sealed scroll compressor | Hermetically sealed scroll compressor | |||
| Weight | Unit | kg | 68 | 103 | 103 | 103 | ||
| Power supply | Phase | 1~ | 1~ | 1~ | 1~ | |||
| Frequency | Hz | 50 | 50 | 50 | 50 | |||
| Voltage | V | 220-240 | 220-240 | 220-240 | 220-240 | |||
| Notes | (1) - Minimum Ssc value: Equipment complying with EN/IEC 61000-3-12: European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and ≤ 75A per phase | (1) - Minimum Ssc value: Equipment complying with EN/IEC 61000-3-12: European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and ≤ 75A per phase | (1) - Minimum Ssc value: Equipment complying with EN/IEC 61000-3-12: European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and ≤ 75A per phase | (1) - Minimum Ssc value: Equipment complying with EN/IEC 61000-3-12: European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and ≤ 75A per phase | ||||
| (2) - Ssc: Short-circuit power | (2) - Ssc: Short-circuit power | (2) - Ssc: Short-circuit power | (2) - Ssc: Short-circuit power | |||||
| (3) - See separate drawing for electrical data | (3) - See separate drawing for electrical data | (3) - See separate drawing for electrical data | (3) - See separate drawing for electrical data | |||||
| (4) - Contains fluorinated greenhouse gases | (4) - Contains fluorinated greenhouse gases | (4) - Power supply to the FDQ indoor unit is separate | (4) - Contains fluorinated greenhouse gases | |||||
| (5) - Contains fluorinated greenhouse gases | ||||||||